QwikCheck® is ideal for preventive maintenance checks and for verifying proper acid clean up. The QwikCheck® indicator paper is golden yellow before testing and will turn pink or red upon being exposed to as little as 1 part per million (PPM) of acid.
Perform a Qwik acid test on operating systems. Ideal for preventative maintenance checks or for verifying proper acid clean-up after a compressor burn-out / change-out.
- 2-Second Refrigeraiton Acid Test
- Test to ARI-700 limit of 1 PPM
- Tests for Inorganic Acid (including POE)
- Meets EPA Venting Rules
Directions
- Insert the valve core depressor into the center of the suction side of the vapor service valve while the system is operating.
- Allow vapor to flow through the QwikCheck® for 3-seconds. If the indicator paper does not change color, hold for another 3-seconds. If the indicator paper still does not change color, inorganic acid was not detected.